Who this page is for. The story page makes a claim: a day of AI questions costs about a teaspoon of water and under two minutes of television. This page is the receipt for it. It walks through every number in the order it was worked out, with the formula, the source, and what each figure does and doesn't count, so that an engineer, a journalist or a determined skeptic can rebuild the whole thing and find any mistake.

You don't need to read it to trust the story page; you need to know it exists. If you're here because something on the story page didn't sit right, start with what would change these conclusions, which says up front where the argument is weakest. If you just want the numbers, they're in the appendix and downloadable below.

This is not a bibliography. It is the derivation, written out in the order it was actually done, so that someone can read it start to finish and rebuild every number on the story page. Every figure carries a scope tag, because most public confusion on this subject comes from comparing figures of different scope. Every number is a link to its entry in the appendix at the bottom. The story page shows US units; the verified metric values are here and on every source chip. Assumptions marked adjustable are shared with the story page.

Dataset last verified . Download the full set as JSON or CSV.

  1. 1. The building
  2. 2. The power
  3. 3. The tokens
  4. 4. The user
  5. 5. The water
  6. 6. The comparisons
  7. 7. The aggregate
  8. Household bills
  9. 8. What would change these conclusions
  10. Appendix: every figure
  11. This page's own footprint

1. The building

The model starts from a reference design rather than from a published per-prompt figure, because a building can be audited and a per-prompt figure cannot. The reference is a Basis of Design for a 100 MW facility, Rev 03-S. Critical IT means the power available to the computing equipment itself, after the facility's own overhead is excluded. Of that, 80% goes to GPU compute, 80 MW; the rest is storage and network.

The compute is entirely GB300 NVL72 racks. A rack draws 145 kW on average across a mixed workload: inference runs at 110 to 150 kW, training at 130 to 180. The rack count follows directly.

racks = 80 MW × 1,000 ÷ 145 kW = 552 GPUs = 552 × 72 = 39,744

The building is about ≈216,000 SF, 600 by 360 ft, with 4 data halls of about ≈24,000 SF each. The site is about ≈140 acres, most of it the chiller yard: 620 by 400 ft, with ≈60 chillers of 630 tons on a 62 ft grid, air-cooled, N+1, with integrated free cooling. Electrical distribution is ≈60 line-ups of 2 MW, distributed redundant in a 5-to-make-4 arrangement. Liquid cooling captures 93% of the heat at the chip; the residual is airside, for network and storage. Staffing is 24 to 30 people.

The building's domestic water, for the people in it, is about ≈2,000 L/day. Divided over the users it serves that is 0.7 µL per user-day, and it is the only water term the narrative does not bother to draw.

2. The power

Power usage effectiveness is total facility energy divided by IT energy. A PUE of 1.20 means that for every kilowatt-hour the computers use, the building uses another 0.20 for cooling, power conversion and lighting. It is a ratio of energies over a period, so the number depends on the period.

The peak design PUE of this building is 1.35 PUE: the W32 design lane, five-year extreme ambient, 100% IT load. That is what the chillers are sized for and it is not an operating point. Annualized, with free cooling available whenever the outdoor air is below the 32 °C facility supply temperature, the design lands at 1.20 PUE. The headline scenario uses 1.20, inside that band and slightly conservative. For comparison, Uptime Institute's industry average is 1.52 PUE, flat for seven years; hyperscale fleets report 1.08 to 1.12 PUE; Google's fleet reports 1.09 PUE; new AI builds land at 1.15 to 1.25 PUE.

This design pays for its zero water in electricity. Dry cooling costs an additional 0.30 to 0.74 kWh/kWh per kWh of IT load against evaporative cooling, and that electricity has its own water footprint at the plant. Section 5 counts it.

3. The tokens

Energy per user depends on how many tokens the fleet actually processes per second, which is much lower than the benchmark number. Start from a benchmark blended throughput of 500,000 tok/s per rack and derate it three times, each factor named.

The derate stack
StepFactorResult, tok/s per rack
Benchmark blended throughput500,000
Serving duty cycle: diurnal peak-to-average, time-to-first-token SLA headroom, spare capacity0.65×325,000
Inference share of the compute block: training, RL and evals draw full power and yield no user tokens0.70×227,500
Real traffic versus benchmark recipe: imperfect batching, ragged context0.90×205,000
Fleet average2.5÷200,000
fleet = 552 racks × 200,000 = 110.00 million tok/s = 9.50 trillion tokens per day

Reality anchor. OpenAI has stated it processes 15.00 billion tokens/min on the API, which is 21.60 trillion tokens/day. At 200,000 tok/s per rack that is ≈1,250 racks, roughly ≈181 MW of GB300 compute. OpenAI's actual fleet is far larger, for three reasons that do not undermine the model: most of the installed base is Hopper and Ampere, and NVIDIA cites 90 tok/s per GPU on Hopper against 6,000 tok/s per GPU on GB300, a 67× gap; training consumes an enormous share; and they are building for future demand. The model here describes what a modern inference fleet costs per token, which is the question a per-person figure needs answered.

4. The user

A day of AI use is taken as 8,000 tokens processed. Processed tokens include the prompt, the context the model re-reads on every turn, any hidden reasoning tokens, and the output. That is far more than the words on screen, and it is why this figure is a fair one for a person who sends about ≈4 substantial prompts a day with some back-and-forth. It is also why the per-prompt spread in published figures is so wide: a reasoning model can spend thousands of hidden tokens on one answer.

Wh per user-day = tokens × (100 MW × PUE ÷ 110.00 million tok/s) ÷ 3,600 = 8,000 × (100,000,000 W × 1.20 ÷ 110,000,000) ÷ 3,600 = 2.42 Wh

The whole-facility 100 MW is used, not the 80 MW compute block, because the storage and network that yield no tokens still draw power on the user's behalf. Users served by one building: 9.50 trillion tokens ÷ 8,000 = ≈1.19 billion users.

Per prompt, the same day is 0.605 Wh at datacenter scope, and 0.47 mL of water at roughly 700 processed tokens per query, the basis used in the almond correction in Act 7. Published anchors bracket this: Google's own measurement of the median Gemini Apps text prompt, May 2025, is 0.24 Wh at datacenter scope, excluding network, device and training own disclosure; Sam Altman's stated average ChatGPT query is 0.34 Wh own disclosure; EPRI's estimate for a ChatGPT prompt is 2.9 Wh against 0.3 Wh for a traditional search independent estimate; reported GPT-5 averages run to ≈18 Wh with heavy responses to 40 Wh third-party estimate.

Worked example, live

Scenario: Average modern AI build. These inputs are shared with the story page. Changing them here changes the receipt in part 6 there.

PUE, adjustable
WUE, L/kWh, adjustable
Grid water, L/kWh, adjustable
Tokens per day, adjustable
Electricity price, $/kWh, adjustable
 
Wh = 8,000 × (100,000,000 × 1.20 ÷ 110,000,000) ÷ 3,600 = 2.42 Wh on site = 0.50 L/kWh × (Wh ÷ PUE) = 1.01 mL at the plant = 1.8 L/kWh × Wh = 4.35 mL water = 5.36 mL per user-day year = 0.88 kWh, 1.96 L, about ≈6 cents, about 8.3 cups of water television = 91 s electricity, 112 s water, at 1.60 Wh and 2.88 mL per minute

The cost line uses 0.068 $/kWh, the price implied by "about six cents" at 0.88 kWh, roughly a US industrial tariff. A residential tariff about doubles the cents and changes nothing else on the site.

5. The water

Water use effectiveness is liters of water consumed on site per kilowatt-hour of IT load. It counts evaporation from cooling towers and adiabatic pre-coolers, and it counts nothing upstream. An air-cooled, closed-loop building has a WUE near 0.0 L/kWh: the coolant loop is sealed and the chillers reject heat to air. The headline scenario uses 0.50 L/kWh, an average for a modern hybrid build, deliberately not the reference design's zero.

The larger term is indirect. Thermoelectric generation evaporates water in its own cooling towers, and hydro reservoirs evaporate water from their surface. The US thermal-fleet average used throughout is 1.8 L/kWh. Alternatives, all adjustable above: 1.2 L/kWh for a gas combined-cycle heavy grid; 3.1 L/kWh from Li, Yang, Islam and Ren; and 4.5 L/kWh for the 2023 US national figure including reservoir evaporation, which is 211.00 billion gallons against 176 TWh.

At the headline assumptions the split is 1.01 mL on site and 4.35 mL at the plant: 19% and 81%. Indirect dominates in every scenario, which is why Google's site-only 0.26 mL per prompt and Sam Altman's site-only 0.32 mL per query are both smaller than the figures here. Shaolei Ren of UC Riverside criticised the Google figure for excluding generation water. The criticism is correct, it applies equally to the Altman figure, and it is why this site counts grid water in every row.

Per user-day by scenario
ScenarioPUEWUEGridWhWater, mL (site / plant)
Best-in-class new build, gas and wind grid1.150.101.22.322.98 (0.20 / 2.78)
Average modern AI build, headline1.200.501.82.425.36 (1.01 / 4.35)
Reference design as built1.200.01.82.424.35 (0 / 4.35)
Legacy evaporative, hot climate1.401.801.82.828.70 (3.63 / 5.08)
Evaporative plus hydro-heavy grid1.401.804.52.8216.31 (3.63 / 12.69)

The worst scenario on the table is 16.31 mL, about three times the headline. It is still under a tablespoon. The dry-cooling trade is the honest one: about ≈2.15 L/kWh saved on site per kWh of IT load, for 0.30 to 0.74 kWh/kWh of extra electricity, which at 1.8 L/kWh evaporates roughly 0.5 to 1.3 L per kWh of IT load at the plant. A net saving of water, paid in electricity, and the reason the narrative says air cooling moves water rather than eliminating it.

The landscape: AWS reports 0.12 L/kWh fleet-wide, from 0.02 L/kWh in Stockholm to 2.85 L/kWh in Jakarta, a 140× spread inside one operator. Equinix reports 0.91 L/kWh. Microsoft's regional figures include 0.02 L/kWh in Singapore and 1.52 L/kWh in Arizona; see the notes in the appendix on what could and could not be confirmed against Microsoft's own documents. The legacy industry average is 1.8 to 1.9 L/kWh. Best-in-class runs under < 0.05. Nevada's rule is the Southern Nevada Water Authority's moratorium on evaporative cooling in new commercial and industrial buildings; Singapore's roadmap sets a target of 2 L/kWh or lower.

6. The comparisons

The television

The site's unit is one minute of a 96 W television. That wattage is not chosen here; it is reverse-derived from Google's own framing that a 0.24 Wh prompt is "less than nine seconds of TV" (0.24 Wh ÷ 9 s × 3,600 = 96 W). The site is extending Google's unit, not inventing one. Google's water framing, "about five drops", implies the same site-only scope as its 0.26 mL.

per minute, set only: 96 W × 60 s = 1.60 Wh; 0.0016 kWh × 1.8 L/kWh = 2.88 mL per minute, full chain: 400 Wh ÷ 180 min = 2.22 Wh; 730 mL ÷ 180 min = 4.06 mL
The claim at both scopes
PairingAI dayElectricityWater
Datacenter-only AI against the set's own draw2.42 Wh / 5.36 mL91 seconds112 seconds
Full delivery chain, both sides3.4 Wh / 7 mL92 seconds105 seconds
Full-chain AI against a set-only television scope mismatch, refused3.4 Wh / 7 mL128 seconds146 seconds

Every consistent pairing lands between 90 and 112 seconds. The mismatched pairing reaches 146 seconds and breaks the two-minute claim, which is exactly the kind of scope mixing that this page criticises in others. The scope field in the dataset prevents the narrative from rendering it; the comparison function refuses the pairing rather than labelling it.

The digital day

The full-chain rows in Act 5 split each activity into device, network and datacenter. Streaming uses the IEA allocation of 72% devices, 23% network and 5% datacenters, anchored on the same 96 W television for three hours: 288 Wh on the set. Network intensity is the weakest input: 0.02 kWh/GB fixed and 0.06 kWh/GB mobile, the 2019 IEA range halved for efficiency gains since. Published kWh/GB estimates span an order of magnitude, and the uncertainty runs in AI's favor: older, higher figures make streaming look worse, not AI. The social media datacenter figure, 13 Wh, is Meta's disclosed datacenter electricity divided by daily active people. Usage is 2 h 21 min h of social media a day globally and about ≈7 h of total US screen time. Device draws implied by those rows, ≈3 W for a phone and 30 W for a laptop, are reused for this page's footprint below.

The objects

Almond. 3.56 L per nut, slightly under a gallon, as attributed in press coverage to a 2019 USGS-affiliated study. The Fulton, Norton and Shilling paper linked in the appendix reports about 12 L per kernel on a different basis; if that basis were used, every almond comparison on the site would move further in AI's favor. The figure used is the smaller one.

Hamburger. The narrative says "a fast-food hamburger" and this page gives the basis: a McDonald's hamburger, 1.6 oz raw patty (45 g) plus bun and condiments. At the global-average beef footprint of 15,400 L/kg (Mekonnen and Hoekstra, 2012) the patty alone is about 700 L and the sandwich about 800 L; at a US feedlot figure it is about 330 L. ≈500 L is the planning central and the range is carried on the figure.

Delivery. One parcel, from the sorting depot to the door. The drive is a class 4 diesel step van on a suburban route, UPS-derived: 100 miles, 151 packages, 8.7 gallons of diesel, 7.8 MJ per parcel, which this site converts to 2.2 kWh (Stolaroff et al., 2018). The same paper gives the carrier's facilities, from UPS's 2015 company-wide totals divided by packages delivered: 0.35 kWh of electricity and 0.93 MJ of natural gas per package, 0.26 kWh as energy. Together, 2.81 kWh. Only the facility electricity carries power-plant water, 630 mL at the site's grid intensity. The warehouse that stored the item, the packaging and the long-haul leg are not counted; no defensible per-parcel figure exists for them, and each would make the parcel larger. An electric truck on the same route is 0.72 kWh at the plug; a small electric van on a dense city route is 0.13 kWh (Rodrigues et al., 2022); a gasoline van at half a mile between stops is 1.0 to 1.6 kWh well-to-wheel (Li, Kim and Keoleian, 2021). No carrier publishes a per-parcel energy figure.

Grid water for electric things. Anything electric on the story page gets its water the same way the AI figure does: the electricity times 1.8 L/kWh. A phone charge is 23 mL; boiling the water for a cup of coffee, 23.7 Wh, is 43 mL; heating a shower is 4.1 L; an electric-car mile is 540 mL.

Coffee, two ways. The 140 L per cup on the story page is the total footprint, almost all of it rain on the plantation. Water Footprint Network's own split puts the pumped share at about 1.0 L per cup, from 139 cubic meters per tonne of roasted coffee at 7 grams a cup. The story page uses the total, as it does for the hamburger, and says so.

Toilet. 6 L per flush matches the federal maximum of 1.6 gal in force since 1994. WaterSense toilets use 1.28 gallons or less; older toilets up to 6.

Shower. 65 L for eight minutes, and 2,270 Wh to heat it. Coffee, egg, bread, t-shirt. Water Footprint Network product footprints: 140 L, 200 L, 40 L, 2,700 L. Streaming hour. ≈133 Wh, one third of the three-hour row.

Blue versus green. Blue water is withdrawn from rivers, lakes and aquifers and consumed. Green water is rainfall held in the soil and transpired by plants. The comparison objects are total footprints, blue and green together; the AI figure is blue plus generation water. That mismatch is labelled in Act 2 and it runs against AI. The distinction matters most for beef in Section 7.

The almond correction

The widely circulated figure of 38,000 queries per almond does not reconcile with Altman's own 0.32 mL per query: 3.56 L ÷ 0.32 mL = 11,125 queries. Reaching 38,000 needs 0.094 mL per query, 3.4× lower than stated. This site's model at 0.47 mL per query gives about ≈7,500 queries. Directionally the claim is right; the arithmetic as quoted is not; and scoped consistently on site against the Act 4 reference design the ratio is infinite, so the argument is stronger than it was made.

7. The aggregate

US annual blue water, national scale, same metric. All US datacenters in 2023, direct plus indirect: 0.80 trillion L (LBNL). US golf courses, 2024 data: 1.59 trillion L, from GCSAA's 1.63 million acre-feet applied, net of the 21% reclaimed share. California almonds alone: 2.59 trillion L from 2.1 million acre-feet applied, or 4.70 trillion L on the higher footprint estimate. US beef, blue water only: 6.76 trillion L. US beef, total footprint including rainfall on pasture: 62.4 trillion L, of which most is green water and would have fallen regardless. Per US resident on 340.00 million people: datacenters 2,353 L, golf 4,672 L, almonds 7,619 L, beef 19,897 L.

Vintage and verification. LBNL reports about 66 billion liters direct and nearly 800 billion liters indirect for 2023, so the 0.80 figure matches the indirect term and understates the total by roughly 8%. That understatement runs in AI's favor and is recorded on the figure rather than corrected silently, because the brief's number is the one the narrative was built on. LBNL's 2025 Update, published June 2026, puts 2024 at 192 TWh (4.7%), 2028 at 464 TWh, and 2030 at 649 TWh; the original brief's 1,050 TWh for 2030 was BCG's high case and is no longer used. Rystad projects datacenter water consumption could roughly triple by 2030, with 34% of direct consumption in high-water-stress regions. S&P Global finds 43% of datacenters globally already exposed to high water stress.

datacenters in year y = 0.80 × (1 + (≈3 − 1) × (y − 2023) ÷ 7); passes golf (1.59) in 2,026

On a straight line to triple, the datacenter bar passes golf in 2,026 and reaches 2.40 trillion L in 2030, still below almonds and well below beef's blue water. The story page says so in one sentence rather than leaving it to a critic.

Electricity, national

All US datacenters used 176 TWh in 2023, 4.4% of US electricity by LBNL's count, which excludes cryptocurrency mining. Against retail sales of 3,874 TWh the share is 4.5%. The story page sets that beside three household uses nobody proposes to switch off, from the EIA's 2020 Residential Energy Consumption Survey: home air conditioning 254 TWh (6.6% of retail sales), electric water heaters 156 TWh (4.0%), electric clothes dryers 56 TWh (1.4%). The household figures are 2020 survey data against 2023 sales, which the story page states. LBNL's 2025 Update projects 464 TWh for 2028 and 649 TWh for 2030, a range of 521 to 843 TWh.

chips' share of a datacenter's electricity = 1 ÷ PUE = 1 ÷ 1.20 = 83%; the rest, 17%, is cooling, power conversion and lights

Household bills: the evidence in both directions

The story page says a datacenter can raise household bills and that it depends on where you live. Four findings stand behind that, chosen because each comes from a government body, a national laboratory or an independent market monitor.

Virginia. The state's legislative auditor projected that a typical Dominion household's generation and transmission charges could be $14 to $37 a month higher by 2040, in constant dollars, depending on how much demand arrives. The same report found that datacenters "are currently paying full cost of service, but growing energy demand is likely to increase costs for other customers." It covers one utility and one part of the bill. As a yearly amount it is $168 to $444 a year; the figure is the increase in the monthly bill by 2040, not a total over the period.

Proportion. The US average residential price rose from 13.15 cents/kWh in 2020 to 17.30 cents/kWh in 2025, 32% before inflation. The Energy Information Administration does not attribute a share of that to datacenters; its own analysis points to capital spending on aging generation and delivery infrastructure. In Virginia, the regulator's November 2025 order raised the typical residential bill by $11.24 a month for 2026 without attributing the increase to datacenters. Datacenters are one driver of bills among several, and the story page says so.

The mid-Atlantic grid. PJM's independent market monitor attributes $29.4 billion, 46.2% of capacity charges across the last four auctions, to datacenter demand, existing and forecast. These are wholesale costs from a counterfactual simulation, and they reach household bills to different degrees by state and utility. The monitor's widely quoted larger percentages are increases over its simulated no-datacenter case, not shares of the total, and are not used here.

The other direction. Lawrence Berkeley National Laboratory and Brattle found that load growth "has tended to depress retail electricity prices in recent years, by spreading fixed costs over greater load": 0.6 cents/kWh lower for a 10% rise in a state's use from 2019 to 2024, a pattern their April 2026 update found still held through 2025. Households benefited less than businesses, and the authors warn the past "need not be prelude," naming PJM as the counter-example.

Rules adopted since 2025. Ohio's commission approved a tariff for new datacenters in July 2025; Indiana's approved large-load terms in February 2025; Georgia's adopted a rule in January 2025; Virginia's created a separate rate class in November 2025. Each requires long contracts and minimum payments. In June 2026 the Federal Energy Regulatory Commission ordered all six regional grid operators to justify or reform how they connect large loads and recover their costs.

Not used, and why. No primary source gives a national dollars-per-household figure, so none appears. A consumer advocate's per-month estimates for Maryland describe the whole capacity price jump, not the datacenter share. Savings claimed by utilities, an industry-funded preprint finding that datacenters lowered rates, a law school paper arguing costs are being shifted, and a Federal Reserve Bank of Dallas working paper estimating a rise in wholesale prices are all informative and all contested; they are named here rather than quoted on the story page.

8. What would change these conclusions

  • The per-person figure is small. It would move materially if fleet throughput were below about 50,000 tok/s per rack (a further 4× derate), if a typical day were above about 50,000 processed tokens, or if the median user were on a reasoning model at 18 Wh per prompt. Any of those would put a typical day at 10 to 45 minutes of television. None would put it at an hour of streaming.
  • The water is at the power plant. It would be false for a building with WUE above about 2.5 L/kWh on a low-water grid, such as an evaporative build in a hot climate on gas combined-cycle. Those buildings exist and are the ones being banned.
  • AI loses to golf on a national scale. It stops being true in 2,026 on the straight line above, and earlier if LBNL's direct term is added. The site says so.
  • The two-minute claim. It would fail if the television were materially less than 96 W (a 40 W set makes the day about four minutes of it), if the 8,000-token day were doubled, or if a mismatched pairing were allowed. The first two are honest disagreements about the median; the third is not allowed.
  • Siting. Nothing here would change the conclusion that averages do not answer a local question, because the site does not claim they do.

Appendix: every figure

Each row is the entry behind a clickable number on the narrative page. Scope tags: datacenter-only counts the building and, where stated, the generating plant; full-chain adds device and network; device-only is the appliance's own draw; blue-water and total-water are the hydrological scopes. Kind tags distinguish a company's own disclosure from an independent estimate and from figures derived on this site.

figures.json figures.csv

Figurevalue, scope, source, and the arithmetic
Every figure on the site (300)
FigureValueScope, kindSourceDerivation and notes
bldg-critical-it
critical IT capacity
100 MWdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
bldg-compute-share
share of critical IT to GPU compute
80%datacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

The other 20% is storage and network.

bldg-compute-mw
GPU compute block
80 MWdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
100 MW × 80%inputs: bldg-critical-it, bldg-compute-share
rack-power
average rack power, GB300 NVL72
145 kW
110 to 180
datacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

Training 130 to 180 kW, inference 110 to 150 kW.

racks
GB300 NVL72 racks
552 racksdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
80,000 kW ÷ 145 kWinputs: bldg-compute-mw, rack-power
gpus-per-rack
GPUs per NVL72 rack
72 GPUsdatacenter-only own-disclosureNVIDIA, 2025. GB300 NVL72 inference throughput versus Hopper
verified 2026-10-01
gpus
GPUs in the reference building
39,744 GPUsdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
552 × 72inputs: racks, gpus-per-rack
pue-peak
peak design PUE
1.35 PUEdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

W32 lane, 5-year extreme ambient, 100% IT load. An upper bound, not an operating point.

pue-annual
annualized PUE, reference design
1.20 PUE
1.15 to 1.22
datacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

Free cooling at 32 °C facility supply. The headline scenario uses 1.20, inside this band.

wue-reference
WUE of the reference design
0.0 L/kWhdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

Closed-loop direct liquid cooling, air-cooled chillers, no evaporative makeup. Approximately zero on site.

chillers
air-cooled chillers
≈60 chillersdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

630-ton each, N+1, six blocks of ten, integrated free cooling.

chiller-tons
chiller capacity, each
630 tonsdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
lineups
modular electrical line-ups
≈60 line-upsdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

Distributed redundant, 5-to-make-4.

lineup-mw
electrical line-up rating, each
2 MWdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
heat-capture
liquid heat capture, nominal
93%
88 to …
datacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

88% minimum. The residual 12% is airside, for network and storage.

bldg-area
building area
≈216,000 SFdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
halls
data halls
4 hallsdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
hall-area
area per data hall
≈24,000 SFdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
bldg-length
building length
600 ftdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
bldg-width
building width
360 ftdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
site-acres
site area
≈140 acresdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
yard-length
chiller yard length
620 ftdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
yard-width
chiller yard width
400 ftdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
chiller-grid
chiller plant grid spacing
62 ftdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
staff
staff on site
24 to 30 people
… to 30
datacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01

24/7/365.

domestic-water
on-site domestic water, whole building
≈2,000 L/daydatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
domestic-water-per-user
domestic water per user-day
0.7 µLdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
2,000 L ÷ 1.19 billion usersinputs: domestic-water, users-daily
tok-benchmark
benchmark blended throughput
500,000 tok/s per rackdatacenter-only own-disclosureNVIDIA, 2025. GB300 NVL72 inference throughput versus Hopper
verified 2026-10-01
derate-duty
serving duty cycle
0.65×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Diurnal peak-to-average, time-to-first-token SLA headroom, spare capacity.

derate-inference
inference share of the compute block
0.70×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Training, RL and evals draw full power and yield no user tokens.

derate-traffic
real traffic versus benchmark recipe
0.90×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Imperfect batching, ragged context.

derate-total
total derate
2.5÷datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1 ÷ (0.65 × 0.70 × 0.90)inputs: derate-duty, derate-inference, derate-traffic
tok-fleet
fleet-average throughput
200,000 tok/s per rackdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
500,000 ÷ 2.5inputs: tok-benchmark, derate-total
fleet-tok-s
fleet throughput
110.00 million tok/sdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
552 racks × 200,000 tok/sinputs: racks, tok-fleet
fleet-tok-day
fleet tokens per day
9.50 trillion tokens/daydatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
110 M tok/s × 86,400 sinputs: fleet-tok-s
tokens-per-user-day
tokens processed per user per day
8,000 tokensdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Processed tokens: prompt, context, hidden reasoning, and output. Not words on screen.

users-daily
daily users served by one reference building
≈1.19 billion usersdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
9.5 trillion ÷ 8,000inputs: fleet-tok-day, tokens-per-user-day
prompts-per-day
prompts in an 8,000-token day
≈4 promptsdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
openai-tok-min
OpenAI API throughput, stated, March 2026
15.00 billion tokens/mindatacenter-only own-disclosureOpenAI, 2026. Accelerating the next phase of AI, 31 March 2026: over 15 billion tokens per minute on the API (6 billion was stated at DevDay, October 2025)
verified 2026-10-01

6 billion per minute was the figure stated in October 2025.

openai-tok-day
OpenAI API tokens per day
21.60 trillion tokens/daydatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
15 billion × 1,440 mininputs: openai-tok-min
openai-racks-equiv
GB300 racks to serve OpenAI API volume
≈1,250 racksdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
21.6 trillion ÷ 86,400 ÷ 200,000inputs: openai-tok-day, tok-fleet
openai-mw-equiv
GB300 compute to serve OpenAI API volume
≈181 MWdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1,250 racks × 145 kWinputs: openai-racks-equiv, rack-power
hopper-tok-gpu
Hopper inference throughput
90 tok/s per GPUdatacenter-only own-disclosureNVIDIA, 2025. GB300 NVL72 inference throughput versus Hopper
verified 2026-10-01
gb300-tok-gpu
GB300 inference throughput
6,000 tok/s per GPUdatacenter-only own-disclosureNVIDIA, 2025. GB300 NVL72 inference throughput versus Hopper
verified 2026-10-01
hopper-gap
GB300 to Hopper throughput gap
67×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
6,000 ÷ 90inputs: gb300-tok-gpu, hopper-tok-gpu
pue
PUE, average modern AI build
1.20 PUEdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
wue
WUE, average modern AI build
0.50 L/kWhdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
grid-water
grid water intensity, US thermal average
1.8 L/kWhdatacenter-only governmentUSGS, 2023. Thermoelectric water consumption, reanalysis 2008 to 2020; per-kWh intensities derived from consumption and generation
verified 2026-10-01

Water evaporated at the generating plant per kWh delivered. The largest single term in the water figure.

grid-water-ccgt
grid water intensity, gas combined-cycle heavy
1.2 L/kWhdatacenter-only governmentUSGS, 2023. Thermoelectric water consumption, reanalysis 2008 to 2020; per-kWh intensities derived from consumption and generation
verified 2026-10-01
grid-water-li
grid water intensity, Li et al.
3.1 L/kWhdatacenter-only academicLi, Yang, Islam and Ren, 2023. Making AI Less Thirsty: uncovering and addressing the secret water footprint of AI models
verified 2026-10-01
grid-water-us2023
grid water intensity, US national 2023 including hydro reservoir evaporation
4.5 L/kWhdatacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01
211 billion gallons ÷ 176 TWhinputs: dc-water-us-gallons, dc-twh-2023
dc-water-us-gallons
US datacenter water, direct plus indirect, 2023
211.00 billion gallonsdatacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01

211 billion gallons is about 800 billion L, which LBNL reports as the indirect (power plant) term for 2023.

ai-day-wh
one day of AI use, electricity
2.42 Whdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
8,000 tokens × (100 MW × 1.20 PUE ÷ 110 M tok/s) ÷ 3,600inputs: tokens-per-user-day, bldg-critical-it, pue, fleet-tok-s
ai-day-ml
one day of AI use, water
5.36 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
site 1.01 mL + grid 4.35 mLinputs: ai-day-ml-site, ai-day-ml-grid

Datacenter scope: cooling water on site plus water evaporated at the power plant to make the electricity. Excludes network, device, training, and fab water.

ai-day-ml-site
one day of AI use, water consumed on site
1.01 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.50 L/kWh × (2.42 Wh ÷ 1.20)inputs: wue, ai-day-wh, pue
ai-day-ml-grid
one day of AI use, water evaporated at the power plant
4.35 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1.8 L/kWh × 2.42 Whinputs: grid-water, ai-day-wh
ai-day-site-share
share of the water consumed on site
19%datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1.01 ÷ 5.36inputs: ai-day-ml-site, ai-day-ml
ai-day-grid-share
share of the water evaporated at the power plant
81%datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
4.35 ÷ 5.36inputs: ai-day-ml-grid, ai-day-ml
ai-year-kwh
one year of daily AI use, electricity
0.88 kWhdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2.42 Wh × 365inputs: ai-day-wh
ai-year-l
one year of daily AI use, water
1.96 Ldatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
5.36 mL × 365inputs: ai-day-ml
ai-year-cents
one year of daily AI use, electricity cost
≈6¢datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.88 kWh × priceinputs: ai-year-kwh, price-kwh
price-kwh
electricity price used for the cost line
0.068 $/kWhdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Implied by the brief's "about six cents" at 0.88 kWh. Roughly a US industrial tariff. Adjustable; a residential tariff roughly doubles the cents and changes nothing else.

ai-year-almonds
one year of daily AI use, in almonds
0.55 almondstotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1.96 L ÷ 3.56 Linputs: ai-year-l, almond-l
sc-best-pue
best-in-class new build, PUE
1.15 PUEdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
sc-best-wue
best-in-class new build, WUE
0.10 L/kWhdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
sc-best-wh
best-in-class new build, per user-day
2.32 Whdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
sc-best-ml
best-in-class new build, water per user-day
2.98 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Site 0.20 mL, grid 2.78 mL at 1.2 L/kWh (gas and wind grid).

sc-legacy-pue
legacy evaporative, hot climate, PUE
1.40 PUEdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
sc-legacy-wue
legacy evaporative, hot climate, WUE
1.80 L/kWhdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
sc-legacy-wh
legacy evaporative, per user-day
2.82 Whdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
sc-legacy-ml
legacy evaporative, water per user-day
8.70 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Site 3.63 mL, grid 5.08 mL.

sc-hydro-ml
legacy evaporative on a hydro-heavy grid, water per user-day
16.31 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Site 3.63 mL, grid 12.69 mL at 4.5 L/kWh.

sc-bod-ml
reference design as built, water per user-day
4.35 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Site 0, grid 4.35 mL.

gemini-wh
Google, median Gemini Apps text prompt, electricity
0.24 Whdatacenter-only own-disclosureGoogle, 2025. Measuring the environmental impact of AI inference (median Gemini Apps text prompt, May 2025)
verified 2026-10-01

Includes idle provisioning and datacenter overhead. Excludes network, device, training, and storage.

gemini-ml
Google, median Gemini Apps text prompt, water
0.26 mLdatacenter-only own-disclosureGoogle, 2025. Measuring the environmental impact of AI inference (median Gemini Apps text prompt, May 2025)
verified 2026-10-01

Site cooling water only. Excludes water evaporated at the power plant, which this site counts.

google-pue
Google fleet PUE
1.09 PUEdatacenter-only own-disclosureGoogle, 2025. Measuring the environmental impact of AI inference (median Gemini Apps text prompt, May 2025)
verified 2026-10-01
google-tv-seconds
Google's own framing: one prompt is less than this many seconds of television
9 secondsdatacenter-only own-disclosureGoogle, 2025. Measuring the environmental impact of AI inference (median Gemini Apps text prompt, May 2025)
verified 2026-10-01

Implies a 96 W television. This site adopts that unit.

google-drops
Google's own framing: one prompt is about this many drops of water
≈5 dropsdatacenter-only own-disclosureGoogle, 2025. Measuring the environmental impact of AI inference (median Gemini Apps text prompt, May 2025)
verified 2026-10-01
altman-wh
Sam Altman, average ChatGPT query, electricity
0.34 Whdatacenter-only own-disclosureSam Altman, 2025. The Gentle Singularity (blog post)
verified 2026-10-01

Blog post, not peer reviewed. Datacenter scope.

altman-ml
Sam Altman, average ChatGPT query, water
0.32 mLdatacenter-only own-disclosureSam Altman, 2025. The Gentle Singularity (blog post)
verified 2026-10-01

On-site water only. Excludes generation water.

epri-chatgpt-wh
EPRI, one ChatGPT prompt
2.9 Whdatacenter-only independent-estimateEPRI, 2024. Powering Intelligence: Analyzing Artificial Intelligence and Data Center Energy Consumption
verified 2026-10-01
epri-search-wh
EPRI, one traditional web search
0.3 Whdatacenter-only independent-estimateEPRI, 2024. Powering Intelligence: Analyzing Artificial Intelligence and Data Center Energy Consumption
verified 2026-10-01
gpt5-wh
reported GPT-5 average per response
≈18 Whdatacenter-only independent-estimatePress reports, 2025. Reported per-response energy of GPT-5, University of Rhode Island AI lab estimates
verified 2026-10-01

Third-party estimate. Some responses reported to 40 Wh.

gpt5-heavy-wh
reported GPT-5 heavy response
40 Whdatacenter-only independent-estimatePress reports, 2025. Reported per-response energy of GPT-5, University of Rhode Island AI lab estimates
verified 2026-10-01
model-spread
spread between the lowest and highest published per-prompt figures
75×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
18 Wh ÷ 0.24 Whinputs: gpt5-wh, gemini-wh
heavy-user-tv-min
a heavy reasoning user's day, in minutes of television
45 minutesdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
4 prompts × 18 Wh ÷ 1.60 Wh per minuteinputs: prompts-per-day, gpt5-wh, tv-min-wh
dd-ai-device
AI assistant, device
0.5 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-ai-network
AI assistant, network
0.5 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-ai-dc
AI assistant, datacenter
2.4 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-ai-wh
AI assistant, 8,000 tokens, about 4 prompts, full chain
3.4 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-ai-ml
AI assistant, full chain, water
7 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-ai-dcshare
AI assistant, datacenter share of energy
71%full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-email-device
email, device
30 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-email-network
email, network
1 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-email-dc
email, datacenter
1 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-email-wh
email, 1 hour in a client, about 120 messages, full chain
32 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-email-ml
email, full chain, water
58 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-email-dcshare
email, datacenter share
3%full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-web-device
web browsing, device
45 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-web-network
web browsing, network
6 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-web-dc
web browsing, datacenter
1.5 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-web-wh
web browsing, 1.5 hours on a laptop, full chain
53 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-web-ml
web browsing, full chain, water
95 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-web-dcshare
web browsing, datacenter share
3%full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-social-device
social media, device
7 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-social-network
social media, network
59 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-social-dc
social media, datacenter
13 Whdatacenter-only own-disclosureMeta, 2024. Sustainability report, datacenter electricity, divided by daily active people
verified 2026-10-01
dd-social-wh
social media, 2 h 21 min on a phone, full chain
79 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-social-ml
social media, full chain, water
149 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-social-dcshare
social media, datacenter share
16%full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-stream-device
streaming video, device (television)
288 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
96 W × 3 hinputs: tv-watts
dd-stream-network
streaming video, network
92 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-stream-dc
streaming video, datacenter and CDN
20 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-stream-wh
streaming video, 3 hours HD on a television, full chain
400 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-stream-ml
streaming video, full chain, water
730 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-stream-dcshare
streaming video, datacenter share
5%full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-stream-hours
hours of streaming in the digital day
3 hfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dd-social-hours
daily time on social media, global
2 h 21 min hfull-chain independent-estimateDataReportal, 2025. Digital 2025, daily time on social media
verified 2026-10-01

DataReportal's Digital 2026 report measures social and video feeds together at about 2 h 39 min a day, a different definition; the 2025 like-for-like figure is kept.

us-screen-hours
total daily US screen time
≈7 hfull-chain independent-estimateDataReportal, 2025. Digital 2025, daily time on social media
verified 2026-10-01
dd-stream-screens
how many more screen-widths the streaming bar runs past the social media bar
4 screensfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
floor(400 ÷ 79) − 1inputs: dd-stream-wh, dd-social-wh
an-ai-kwh
AI, annual, full chain
1.3 kWhfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
3.4 Wh × 365inputs: dd-ai-wh
an-ai-l
AI, annual water, full chain
2.7 Lfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-email-kwh
email, annual
12 kWhfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-email-l
email, annual water
21 Lfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-web-kwh
web browsing, annual
19 kWhfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-web-l
web browsing, annual water
35 Lfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-social-kwh
social media, annual
29 kWhfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-social-l
social media, annual water
54 Lfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-stream-kwh
streaming, annual
146 kWhfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-stream-l
streaming, annual water
267 Lfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
an-nonai-kwh
combined non-AI digital life, annual electricity
206 kWhfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
12 + 19 + 29 + 146inputs: an-email-kwh, an-web-kwh, an-social-kwh, an-stream-kwh
an-nonai-l
combined non-AI digital life, annual water
377 Lfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
21 + 35 + 54 + 267inputs: an-email-l, an-web-l, an-social-l, an-stream-l
ai-adds
what AI adds to a non-AI digital life
0.6%full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1.3 kWh ÷ 206 kWhinputs: an-ai-kwh, an-nonai-kwh
iea-device-share
streaming energy share, devices (IEA allocation)
72%full-chain independent-estimateIEA, 2020. The carbon footprint of streaming video: fact-checking the headlines
verified 2026-10-01
iea-network-share
streaming energy share, network (IEA allocation)
23%full-chain independent-estimateIEA, 2020. The carbon footprint of streaming video: fact-checking the headlines
verified 2026-10-01
iea-dc-share
streaming energy share, datacenters (IEA allocation)
5%full-chain independent-estimateIEA, 2020. The carbon footprint of streaming video: fact-checking the headlines
verified 2026-10-01
net-fixed
network intensity, fixed
0.02 kWh/GBfull-chain independent-estimateIEA, 2020. The carbon footprint of streaming video: fact-checking the headlines
verified 2026-10-01

2019 IEA range halved for efficiency gains. Published estimates span an order of magnitude. Older, higher figures make streaming look worse, not AI.

net-mobile
network intensity, mobile
0.06 kWh/GBfull-chain independent-estimateIEA, 2020. The carbon footprint of streaming video: fact-checking the headlines
verified 2026-10-01
phone-watts
phone draw while in use
≈3 Wdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
7 Wh ÷ 2.35 h, from the social media rowinputs: dd-social-device, dd-social-hours
laptop-watts
laptop draw while browsing
30 Wdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
45 Wh ÷ 1.5 h, from the web browsing rowinputs: dd-web-device
flush-l
one toilet flush
6 Ldevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
almond-l
one California almond
3.56 Ltotal-water academicUSGS-affiliated study, 2019, as reported, 2019. Per-nut almond water footprint, 3.56 L; the Fulton, Norton and Shilling 2019 paper linked here reports about 12 L per kernel on a different basis
verified 2026-10-01

Attribution note: press coverage credits a 2019 USGS-affiliated study. The Fulton, Norton and Shilling 2019 paper reports about 12 L per kernel on a different basis, which would make every almond comparison on this site more favorable to AI, not less. Slightly under a gallon. Full embedded-water footprint.

bread-l
one slice of bread
40 Ltotal-water academicWater Footprint Network, 2011. Product water footprints (bread, coffee, egg, cotton)
verified 2026-10-01
shower-l
one 8-minute shower
65 Ldevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
coffee-l
one cup of coffee
140 Ltotal-water academicWater Footprint Network, 2011. Product water footprints (bread, coffee, egg, cotton)
verified 2026-10-01
egg-l
one egg
200 Ltotal-water academicWater Footprint Network, 2011. Product water footprints (bread, coffee, egg, cotton)
verified 2026-10-01
burger-l
one fast-food hamburger
≈500 L
330 to 800
total-water academicMekonnen and Hoekstra, 2012. A global assessment of the water footprint of farm animal products, Ecosystems
verified 2026-10-01

1.6 oz raw patty (45 g) plus bun and condiments. About 800 L at the global-average beef footprint of 15,400 L/kg, about 330 L at a US feedlot figure. 500 L is the planning central.

beef-l-kg
global-average beef water footprint
15,400 L/kgtotal-water academicMekonnen and Hoekstra, 2012. A global assessment of the water footprint of farm animal products, Ecosystems
verified 2026-10-01
tshirt-l
one cotton t-shirt
2,700 Ltotal-water academicWater Footprint Network, 2011. Product water footprints (bread, coffee, egg, cotton)
verified 2026-10-01
flush-days
one toilet flush, in AI user-days
1,120 AI daystotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
6 L ÷ 5.36 mLinputs: flush-l, ai-day-ml
almond-days
one almond, in AI user-days
665 AI daystotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
3.56 L ÷ 5.36 mLinputs: almond-l, ai-day-ml
almond-years
one almond, in years of daily AI use
1.8 AI yearstotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
665 ÷ 365inputs: almond-days
shower-days
one shower, in AI user-days
12,130 AI daystotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
shower-years
one shower, in years of daily AI use
33 AI yearstotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
burger-days
one hamburger, in AI user-days
93,330 AI daystotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
500 L ÷ 5.36 mLinputs: burger-l, ai-day-ml
burger-years
one hamburger, in years of daily AI use
256 AI yearstotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
tshirt-years
one t-shirt, in years of daily AI use
1,380 AI yearstotal-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
led-wh
a 10 W LED bulb for one hour
10 Whdevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
phone-charge-wh
charging a phone
13 Whdevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
boil-wh
boiling a liter of water
100 Whdevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
stream-hour-wh
one hour of HD streaming, full chain
≈133 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
400 Wh ÷ 3 hinputs: dd-stream-wh
ev-mile-wh
one mile in an electric car
300 Whdevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
burger-wh
one fast-food hamburger, primary energy
≈1,100 Whtotal-water academicMekonnen and Hoekstra, 2012. A global assessment of the water footprint of farm animal products, Ecosystems
verified 2026-10-01
fridge-day-wh
a refrigerator for one day
1,500 Whdevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
hot-shower-wh
one 8-minute hot shower
2,270 Whdevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01
home-day-wh
an average US home for one day
29,000 Whdevice-only governmentUS EIA, 2024. Average residential electricity consumption, and thermoelectric generation
verified 2026-10-01

EIA's 2024 figure is about 28,400 Wh a day (865 kWh a month); the brief's 29,000 is kept.

altman-almond-claim
ChatGPT queries per almond, widely circulated version of the claim
38,000 queriesdatacenter-only pressPolitiFact, 2026. Fact check of Sam Altman's remark on the Sources podcast, 1 September 2026, that one almond equals 38,000 ChatGPT queries (rated Mostly False), 4 September 2026
verified 2026-10-01
almond-queries-altman
queries per almond at Altman's own 0.32 mL
11,125 queriesdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
3.56 L ÷ 0.32 mLinputs: almond-l, altman-ml
altman-implied-ml
per-query water implied by 38,000 queries per almond
0.094 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
3.56 L ÷ 38,000inputs: almond-l, altman-almond-claim
altman-gap
gap between the implied figure and the stated figure
3.4×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.32 ÷ 0.094inputs: altman-ml, altman-implied-ml
site-ml-per-query
water per query, this site's bottom-up model
0.47 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

Datacenter scope including generation water, at roughly 700 processed tokens per query.

site-queries-per-almond
queries per almond, this site's model
≈7,500 queriesdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
3.56 L ÷ 0.47 mLinputs: almond-l, site-ml-per-query
wue-best
best-in-class facilities, WUE
< 0.05 L/kWhdatacenter-only industry-surveyUptime Institute, 2026. Global Data Center Survey 2026 (industry average PUE 1.52; 1.54 in 2025, 1.56 in 2024, 1.58 in 2023)
verified 2026-10-01
wue-aws
AWS fleet-wide WUE, 2025
0.12 L/kWhdatacenter-only own-disclosureAmazon Web Services, 2025. AWS water positive: WUE by region, 2025 report
verified 2026-10-01
wue-aws-stockholm
AWS, Stockholm, WUE
0.02 L/kWhdatacenter-only own-disclosureAmazon Web Services, 2025. AWS water positive: WUE by region, 2025 report
verified 2026-10-01
wue-aws-jakarta
AWS, Jakarta, WUE
2.85 L/kWhdatacenter-only own-disclosureAmazon Web Services, 2025. AWS water positive: WUE by region, 2025 report
verified 2026-10-01
wue-aws-spread
spread inside AWS's own portfolio
140×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2.85 ÷ 0.02inputs: wue-aws-jakarta, wue-aws-stockholm
wue-equinix
Equinix WUE, 2025
0.91 L/kWhdatacenter-only own-disclosureEquinix, 2025. Sustainability data summary (0.95 all sites in 2024 data; the 0.91 figure is as reported by Rystad, October 2025)
verified 2026-10-01

Secondary reports of Equinix's own 2025 data give 0.91 across all sites and 1.41 at evaporatively cooled sites. As reported by Rystad Energy, October 2025. Equinix's own 2024 data summary states 0.95 across all sites.

wue-google-msft
Google and Microsoft fleet WUE
well under 1.0 L/kWhdatacenter-only own-disclosureMicrosoft, 2026. 2026 Environmental Sustainability Report (FY25): global datacenter WUE 0.27 L/kWh; regional WUE at datacenters.microsoft.com/sustainability/efficiency
verified 2026-10-01
wue-msft-singapore
Microsoft, Singapore, WUE
0.02 L/kWhdatacenter-only own-disclosureMicrosoft, 2026. 2026 Environmental Sustainability Report (FY25): global datacenter WUE 0.27 L/kWh; regional WUE at datacenters.microsoft.com/sustainability/efficiency
verified 2026-10-01

Could not be located in a Microsoft document during verification; Microsoft publishes regional WUE (EMEA 0.03, APAC 0.25, Americas 0.34 for FY25). Treat the site-level figure as unconfirmed.

wue-msft-arizona
Microsoft, Arizona, WUE
1.52 L/kWhdatacenter-only own-disclosureMicrosoft, 2026. 2026 Environmental Sustainability Report (FY25): global datacenter WUE 0.27 L/kWh; regional WUE at datacenters.microsoft.com/sustainability/efficiency
verified 2026-10-01

Could not be located in a Microsoft document during verification. Treat as unconfirmed.

wue-legacy
legacy industry average WUE
1.8 to 1.9 L/kWh
… to 1.9
datacenter-only industry-surveyUptime Institute, 2026. Global Data Center Survey 2026 (industry average PUE 1.52; 1.54 in 2025, 1.56 in 2024, 1.58 in 2023)
verified 2026-10-01
wue-aircooled
air-cooled closed loop, on site
≈0.0 L/kWhdatacenter-only derivedReference Architecture, 2026. Basis of Design, 100 MW GB300 NVL72 facility, Rev 03-S
verified 2026-10-01
pue-global
industry average PUE, 2026 survey
1.52 PUEdatacenter-only industry-surveyUptime Institute, 2026. Global Data Center Survey 2026 (industry average PUE 1.52; 1.54 in 2025, 1.56 in 2024, 1.58 in 2023)
verified 2026-10-01

1.52 in 2026, 1.54 in 2025, 1.56 in 2024, 1.58 in 2023: flat for seven years.

pue-hyperscale
hyperscale fleet PUE
1.08 to 1.12 PUE
… to 1.12
datacenter-only industry-surveyUptime Institute, 2026. Global Data Center Survey 2026 (industry average PUE 1.52; 1.54 in 2025, 1.56 in 2024, 1.58 in 2023)
verified 2026-10-01
pue-new-ai
new AI builds, PUE
1.15 to 1.25 PUE
… to 1.25
datacenter-only industry-surveyUptime Institute, 2026. Global Data Center Survey 2026 (industry average PUE 1.52; 1.54 in 2025, 1.56 in 2024, 1.58 in 2023)
verified 2026-10-01
singapore-wue-cap
Singapore WUE ceiling for new datacenters
2 L/kWhdatacenter-only governmentSingapore IMDA, 2024. Green Data Centre Roadmap, May 2024: WUE target of 2.0 m³/MWh or lower
verified 2026-10-01

The roadmap states a target of 2.0 m³/MWh or lower for new and existing facilities, not a hard ceiling on new builds.

dry-cooling-water-saved
water saved on site by dry cooling, per kWh of IT load
≈2.15 L/kWhdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dry-cooling-energy-cost
additional electricity for dry cooling, per kWh of IT load
0.30 to 0.74 kWh/kWh
… to 0.74
datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01

That electricity has its own water footprint at the power plant. Dry cooling moves water rather than eliminating it.

nevada-ban
Nevada: cooling towers for new datacenters
banneddatacenter-only governmentSouthern Nevada Water Authority, 2025. Moratorium on evaporative cooling in new commercial and industrial buildings, in force for permits from 31 August 2023
verified 2026-10-01

The rule is the Southern Nevada Water Authority's moratorium on evaporative cooling in new commercial and industrial buildings, which covers datacenters, not a state statute.

agg-dc
all US datacenters, 2023, direct plus indirect
0.80 trillion Ldatacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01

Verification note: LBNL reports about 66 billion L direct and nearly 800 billion L indirect for 2023; 0.80 trillion matches the indirect term alone, so the total is understated by roughly 8%. That understatement runs in AI's favor and is flagged rather than hidden. Direct cooling water plus water evaporated at power plants to make their electricity.

agg-golf
US golf courses, 2024
1.59 trillion Lblue-water industry-surveyGCSAA, 2024. Golf Course Environmental Profile Phase IV water report, 2024 data
verified 2026-10-01

1.63 million acre-feet is 2.01 trillion L; net of the 21% reclaimed share it is 1.59 trillion L of fresh blue water. GCSAA's 2024 data puts the recycled share at 19%. 1.63 million acre-feet, 21% of it reclaimed water.

agg-almonds
California almonds alone
2.59 trillion Ltotal-water academicUSGS-affiliated study, 2019, as reported, 2019. Per-nut almond water footprint, 3.56 L; the Fulton, Norton and Shilling 2019 paper linked here reports about 12 L per kernel on a different basis
verified 2026-10-01

2.1 million acre-feet applied.

agg-almonds-high
California almonds, higher footprint estimate
4.70 trillion Ltotal-water academicUSGS-affiliated study, 2019, as reported, 2019. Per-nut almond water footprint, 3.56 L; the Fulton, Norton and Shilling 2019 paper linked here reports about 12 L per kernel on a different basis
verified 2026-10-01
agg-beef-blue
US beef, blue water only
6.76 trillion Lblue-water academicUSDA and Water Footprint Network, 2012. US beef production and per-kilogram water footprint, blue and total
verified 2026-10-01
agg-beef-total
US beef, total footprint including rainfall
62.4 trillion Ltotal-water academicUSDA and Water Footprint Network, 2012. US beef production and per-kilogram water footprint, blue and total
verified 2026-10-01

Mostly green water: rain that fell on pasture and would have fallen regardless.

agg-golf-x
golf versus datacenters
2.0×blue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1.59 ÷ 0.80inputs: agg-golf, agg-dc
agg-almonds-x
almonds versus datacenters
3.2×blue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
agg-almonds-high-x
almonds, high estimate, versus datacenters
5.9×blue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
agg-beef-blue-x
beef, blue water, versus datacenters
8.5×blue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
agg-beef-total-x
beef, total footprint, versus datacenters
78×total-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
us-population
US population
340.00 million peopleblue-water governmentUS Census Bureau, 2024. US population estimate, 340 million
verified 2026-10-01

The Vintage 2025 estimate is 341.8 million; 340 million is kept to match the 2023 aggregates.

pc-dc
datacenters, per US resident per year
2,353 Lblue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.80 trillion ÷ 340 millioninputs: agg-dc, us-population
pc-golf
golf, per US resident per year
4,672 Lblue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
pc-almonds
California almonds, per US resident per year
7,619 Lblue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
pc-beef
beef, blue water, per US resident per year
19,897 Lblue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
dc-twh-2023
US datacenter electricity, 2023
176 TWhdatacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01

Kept as the base year because it matches the latest LBNL water data; 2024 was 192 TWh and 4.7%.

dc-twh-2030
US datacenter electricity, 2030, LBNL reference case
649 TWh
521 to 843
datacenter-only governmentLawrence Berkeley National Laboratory, 2026. United States Data Center Energy Usage Report: 2025 Update, LBNL-2001758, June 2026
verified 2026-10-01

LBNL's 2025 Update gives 649 TWh for 2030, range 521 to 843 (9.5% to 15.3% of US electricity). The original brief's 1,050 TWh was BCG's high case as cited by WRI and is no longer used.

dc-water-growth
projected growth in datacenter water consumption by 2030
≈3×blue-water independent-estimateRystad Energy, 2025. Data center water consumption outlook to 2030
verified 2026-10-01
dc-stress-share
share of direct datacenter water consumption in high-water-stress regions
34%blue-water independent-estimateRystad Energy, 2025. Data center water consumption outlook to 2030
verified 2026-10-01
dc-stress-global
datacenters globally already exposed to high water stress
43%blue-water independent-estimateS&P Global, 2025. Data centers and water stress exposure
verified 2026-10-01
agg-year-base
base year of the aggregate figures
2,023datacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01
agg-year-proj
projection year
2,030datacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01
tv-watts
the television
96 Wdevice-only own-disclosureGoogle, 2025. Measuring the environmental impact of AI inference (median Gemini Apps text prompt, May 2025)
verified 2026-10-01

Reverse-derived from Google's framing that a 0.24 Wh prompt is "less than nine seconds of TV". This site extends Google's unit rather than inventing one.

tv-min-wh
one minute of television, electricity, set only
1.60 Whdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
96 W × 60 sinputs: tv-watts
tv-min-ml
one minute of television, water, set only
2.88 mLdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.0016 kWh × 1.8 L/kWhinputs: tv-min-wh, grid-water
tv-min-wh-full
one minute of television, electricity, full chain
2.22 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
400 Wh ÷ 180 mininputs: dd-stream-wh
tv-min-ml-full
one minute of television, water, full chain
4.06 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
730 mL ÷ 180 mininputs: dd-stream-ml
claim-wh-dc
one AI day in television, electricity, datacenter scope against the set's own draw
91 secondsdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2.42 Wh ÷ 1.60 Wh per minute × 60inputs: ai-day-wh, tv-min-wh
claim-ml-dc
one AI day in television, water, datacenter scope against the set's own draw
112 secondsdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
5.36 mL ÷ 2.88 mL per minute × 60inputs: ai-day-ml, tv-min-ml
claim-wh-full
one AI day in television, electricity, full chain both sides
92 secondsfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
3.4 Wh ÷ 2.22 Wh per minute × 60inputs: dd-ai-wh, tv-min-wh-full
claim-ml-full
one AI day in television, water, full chain both sides
105 secondsfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
7 mL ÷ 4.06 mL per minute × 60inputs: dd-ai-ml, tv-min-ml-full
claim-low
lowest consistent pairing
90 secondsdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
claim-high
highest consistent pairing
112 secondsdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
mismatch-wh
full-chain AI against a set-only television, electricity (scope mismatch)
128 secondsfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
3.4 Wh ÷ 1.60 Wh per minute × 60inputs: dd-ai-wh, tv-min-wh

Not a valid pairing. Shown only to demonstrate what scope mixing does.

mismatch-ml
full-chain AI against a set-only television, water (scope mismatch)
146 secondsfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
7 mL ÷ 2.88 mL per minute × 60inputs: dd-ai-ml, tv-min-ml

Not a valid pairing. It breaks the two-minute claim, which is exactly why the site refuses to render it.

five-min-tv-wh
five minutes of television, electricity
8.0 Whdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
5 × 1.60 Whinputs: tv-min-wh
five-min-tv-ml
five minutes of television, water
14.4 mLdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
5 × 2.88 mLinputs: tv-min-ml
five-min-tv-days
five minutes of television, in days of AI use
≈3 AI daysdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
8.0 Wh ÷ 2.42 Wh; 14.4 mL ÷ 5.36 mLinputs: five-min-tv-wh, ai-day-wh
dd-stream-screens-water
how many more screen-widths the streaming water bar runs past the social media bar
3 screensfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
floor(730 ÷ 149) − 1inputs: dd-stream-ml, dd-social-ml
site-wh-per-prompt
one prompt, this site's model, datacenter scope
0.605 Whdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2.42 Wh ÷ 4 promptsinputs: ai-day-wh, prompts-per-day
site-ml-per-prompt
one prompt, this site's model, water, datacenter scope
1.34 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
5.36 mL ÷ 4 promptsinputs: ai-day-ml, prompts-per-day
chain-wh-per-prompt
device and network electricity per prompt
0.25 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
(0.5 + 0.5 Wh) ÷ 4 promptsinputs: dd-ai-device, dd-ai-network, prompts-per-day
chain-ml-per-prompt
device and network water per prompt
0.41 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
(7 − 5.36 mL) ÷ 4 promptsinputs: dd-ai-ml, ai-day-ml, prompts-per-day
stream-hour-ml
one hour of HD streaming, water, full chain
243 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
730 mL ÷ 3 hinputs: dd-stream-ml, dd-stream-hours
social-hour-wh
one hour of social media, full chain
34 Whfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
79 Wh ÷ 2.35 hinputs: dd-social-wh, dd-social-hours
social-hour-ml
one hour of social media, water, full chain
63 mLfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
149 mL ÷ 2.35 hinputs: dd-social-ml, dd-social-hours
agg-dc-2030
US datacenters, 2030, at roughly triple
2.40 trillion Lblue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.80 × 3inputs: agg-dc, dc-water-growth
agg-dc-passes-golf
year the datacenter bar passes golf on a straight line to triple
2,026blue-water derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2023 + 7 × (1.59 ÷ 0.80 − 1) ÷ 2inputs: agg-dc, agg-golf, dc-water-growth
us-teaspoon
one US teaspoon
4.93 mLdevice-only governmentNIST, 2026. Handbook 44, units of volume
verified 2026-10-01
us-gallon
one US gallon
3.785 Ldevice-only governmentNIST, 2026. Handbook 44, units of volume
verified 2026-10-01
us-cup
one US cup
236.6 mLdevice-only governmentNIST, 2026. Handbook 44, units of volume
verified 2026-10-01
water-bottle
one 16.9-ounce bottle of water
500 mLdevice-only derivedRetail standard, 2026. Standard 16.9 fl oz (500 mL) bottled water
verified 2026-10-01
bottle-days
one bottle of water, in days of AI use
93 AI daysdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
500 mL ÷ 5.36 mLinputs: water-bottle, ai-day-ml
football-field
one football field including end zones
57,600 SFdevice-only industry-surveyNFL, 2025. Official playing rules, field dimensions
verified 2026-10-01
360 ft × 160 ft
bldg-fields
the building, in football fields
3.75 football fieldsdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
216,000 SF ÷ 57,600 SFinputs: bldg-area, football-field
homes-per-rack
average US homes drawing as much power as one rack
120 homesdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
145 kW ÷ (29,000 Wh ÷ 24 h)inputs: rack-power, home-day-wh
meme-ratio
how far the 17-gallons-per-question claim is from this site's per-query figure
137,000×datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
17 gal × 3.785 L ÷ 0.47 mLinputs: us-gallon, site-ml-per-query
meme-gallons
the circulated claim: gallons per question
17 galdatacenter-only pressCirculated claim, 2025. Viral posts, 2023 to 2025, unattributed
verified 2026-10-01
persona-light-wh
"a little": one question a day, datacenter scope
0.605 Whdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1 × 0.605 Whinputs: site-wh-per-prompt
persona-light-ml
"a little": one question a day, water
1.34 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1 × 1.34 mLinputs: site-ml-per-prompt
persona-heavy-wh
"all day for work": four long answers from a heavy reasoning model, datacenter scope
72 Whdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
4 × 18 Whinputs: prompts-per-day, gpt5-wh
persona-heavy-ml
"all day for work": water
≈160 mLdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.50 × (72 ÷ 1.20) + 1.8 × 72inputs: persona-heavy-wh, wue, pue, grid-water
persona-heavy-usd
"all day for work": a year of electricity
1.79 $datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
72 Wh × 365 × $0.068inputs: persona-heavy-wh, price-kwh
stream-year-usd
a year of streaming, electricity
9.93 $full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
146 kWh × $0.068inputs: an-stream-kwh, price-kwh
social-year-usd
a year of social media, electricity
1.97 $full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
29 kWh × $0.068inputs: an-social-kwh, price-kwh
ai-year-usd
a year of AI, electricity, full chain
0.09 $full-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1.3 kWh × $0.068inputs: an-ai-kwh, price-kwh
stream-year-showers
a year of streaming, water, in 8-minute showers
4.1 showersfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
267 L ÷ 65 Linputs: an-stream-l, shower-l
ai-year-almonds-full
a year of AI, water, full chain, in almonds
0.76 almondsfull-chain derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2.7 L ÷ 3.56 Linputs: an-ai-l, almond-l
parcel-diesel-kwh
one parcel, last mile, diesel delivery truck on a suburban route, fuel energy
2.2 kWhlifecycle academicStolaroff et al., 2018. Energy use and life cycle GHG emissions of drones for commercial package delivery, Nature Communications 9:409
verified 2026-10-01

Class 4 diesel step van, UPS-derived base case: 100 miles, 151 packages, 8.7 gallons of diesel; the paper states 7.8 MJ per package, which this site converts to 2.2 kWh. Fuel energy, not electricity, so no power-plant water applies.

parcel-ev-kwh-high
one parcel, last mile, electric delivery truck on the same suburban route
0.72 kWhlifecycle academicStolaroff et al., 2018. Energy use and life cycle GHG emissions of drones for commercial package delivery, Nature Communications 9:409
verified 2026-10-01

2.6 MJ per package at the plug.

parcel-ev-kwh-low
one parcel, last mile, small electric van on a dense city route
0.13 kWhlifecycle academicRodrigues et al., 2022. Last-mile delivery emissions, Patterns 3:100569
verified 2026-10-01

0.47 MJ per package; 1.74 stops per km, two packages per stop.

parcel-facility-kwh
one parcel, the sorting and distribution facilities, electricity
0.35 kWhlifecycle academicStolaroff et al., 2018. Energy use and life cycle GHG emissions of drones for commercial package delivery, Nature Communications 9:409, Methods
verified 2026-10-01

UPS company-wide electricity for 2015 divided by 4.7 billion packages delivered; stated in the paper's Methods, "Emissions from warehouses". The paper treats it as a base case with acknowledged uncertainty in accounting boundaries.

parcel-facility-gas-kwh
one parcel, the facilities' natural gas, as energy
0.26 kWhlifecycle academicStolaroff et al., 2018. Energy use and life cycle GHG emissions of drones for commercial package delivery, Nature Communications 9:409, Methods
verified 2026-10-01
0.93 MJ ÷ 3.6

The paper states 0.93 MJ of natural gas per package, same basis as the electricity. Fuel energy; no power-plant water applies.

parcel-total-kwh
one parcel, depot and last mile together, energy
2.81 kWhlifecycle derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2.2 + 0.35 + 0.26inputs: parcel-diesel-kwh, parcel-facility-kwh, parcel-facility-gas-kwh

Counts the sorting facilities and the final drive. Does not count the warehouse that stored the item, the packaging, or the long-haul trip; each would make it larger.

parcel-facility-ml
one parcel, water at the power plant for the facilities' electricity
630 mLlifecycle derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.35 kWh × 1.8 L/kWhinputs: parcel-facility-kwh, grid-water
parcel-diesel-days
one diesel-delivered parcel, in days of AI, energy
909 AI daysdatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2,200 Wh ÷ 2.42 Whinputs: parcel-diesel-kwh, ai-day-wh
parcel-ev-water-high
one electric-truck parcel, water at the power plant
1.3 Ldatacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
0.72 kWh × 1.8 L/kWhinputs: parcel-ev-kwh-high, grid-water
dc-share-us
all US datacenters as a share of US electricity, 2023
4.4%datacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01

Excludes cryptocurrency mining. Against retail sales alone the share is 4.5%.

dc-twh-2028-low
US datacenter electricity, 2028 projection, low (2024 report)
325 TWhdatacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01

Superseded: the 2025 Update gives a 2028 reference case of 464 TWh.

dc-twh-2028-high
US datacenter electricity, 2028 projection, high (2024 report)
580 TWhdatacenter-only governmentLawrence Berkeley National Laboratory, 2024. 2024 United States Data Center Energy Usage Report (176 TWh and 4.4% in 2023, and the water figures); for electricity, superseded by the 2025 Update of June 2026
verified 2026-10-01

Superseded: the 2025 Update gives a 2028 reference case of 464 TWh.

dc-twh-2028
US datacenter electricity, 2028, LBNL reference case
464 TWhdatacenter-only governmentLawrence Berkeley National Laboratory, 2026. United States Data Center Energy Usage Report: 2025 Update, LBNL-2001758, June 2026
verified 2026-10-01
dc-twh-2024
US datacenter electricity, 2024
192 TWhdatacenter-only governmentLawrence Berkeley National Laboratory, 2026. United States Data Center Energy Usage Report: 2025 Update, LBNL-2001758, June 2026
verified 2026-10-01
dc-share-us-2024
all US datacenters as a share of US electricity, 2024
4.7%datacenter-only governmentLawrence Berkeley National Laboratory, 2026. United States Data Center Energy Usage Report: 2025 Update, LBNL-2001758, June 2026
verified 2026-10-01
us-retail-twh
US retail electricity sales, 2023
3,874 TWhdevice-only governmentUS EIA, 2024. Electric Power Annual, table 2.2, sales to ultimate customers by sector
verified 2026-10-01

2024 retail sales were 3,975 TWh; 2023 is kept so the shares are same-year with the datacenter figure.

ac-twh
US home air conditioning, electricity, 2020
254 TWhdevice-only governmentUS EIA, 2024. 2020 Residential Energy Consumption Survey, tables CE4.1 and CE5.1a
verified 2026-10-01

Occupied primary homes; air handlers for cooling are a further 38 TWh.

waterheat-twh
US electric water heaters, electricity, 2020
156 TWhdevice-only governmentUS EIA, 2024. 2020 Residential Energy Consumption Survey, tables CE4.1 and CE5.1a
verified 2026-10-01
dryer-twh
US electric clothes dryers, electricity, 2020
56 TWhdevice-only governmentUS EIA, 2024. 2020 Residential Energy Consumption Survey, table CE5.1a
verified 2026-10-01
ac-share
home air conditioning as a share of US retail sales
6.6%device-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
254 ÷ 3,874inputs: ac-twh, us-retail-twh

2020 survey against 2023 sales.

waterheat-share
electric water heaters as a share of US retail sales
4.0%device-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
156 ÷ 3,874inputs: waterheat-twh, us-retail-twh
dryer-share
electric clothes dryers as a share of US retail sales
1.4%device-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
56 ÷ 3,874inputs: dryer-twh, us-retail-twh
it-share
share of a datacenter's electricity that reaches the chips
83%datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1 ÷ 1.20 PUEinputs: pue
overhead-share
share of a datacenter's electricity for cooling, power conversion and lights
17%datacenter-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
1 − 1 ÷ 1.20inputs: pue
kettle-cup-wh
boiling the water for one cup of coffee
23.7 Whdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
100 Wh per liter × 0.2366 Linputs: boil-wh, us-cup

Assumes the cup is boiled from cold.

coffee-blue-l
one cup of coffee, blue water only
1.0 Lblue-water academicMekonnen and Hoekstra, 2010. The green, blue and grey water footprint of crops and derived crop products, Value of Water Research Report 47
verified 2026-10-01
139 m³ per tonne roasted × 7 g

The 140 L total is almost all rain on the plantation; about 0.7% is pumped water.

flush-standard-gal
US federal maximum flush volume since 1994
1.6 galblue-water governmentUS EPA, 2024. WaterSense: residential toilets
verified 2026-10-01

WaterSense toilets use 1.28 gallons or less; older toilets up to 6.

bldg-homes
average US homes drawing as much power as the whole building
≈82,800 homesdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
100,000 kW ÷ (29 kWh per day ÷ 24 h)inputs: bldg-critical-it, home-day-wh
phone-charge-ml
charging a phone, water evaporated at the power plant
23 mLdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
13 Wh × 1.8 L/kWhinputs: phone-charge-wh, grid-water
kettle-cup-ml
boiling the water for one cup, water at the power plant
43 mLdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
23.7 Wh × 1.8 L/kWhinputs: kettle-cup-wh, grid-water
hot-shower-ml
heating one shower, water at the power plant
4.1 Ldevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
2,270 Wh × 1.8 L/kWhinputs: hot-shower-wh, grid-water
ev-mile-ml
one electric-car mile, water at the power plant
540 mLdevice-only derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
300 Wh × 1.8 L/kWhinputs: ev-mile-wh, grid-water
bill-va-2040
projected rise in a typical Virginia household's generation and transmission charges by 2040, before inflation
$14 to $37 a month
… to 37
cost governmentVirginia JLARC, 2024. Data Centers in Virginia, Report 598, 9 December 2024
verified 2026-10-01

Dominion residential customer at 1,000 kWh a month, constant 2024 dollars: +$14 at half of unconstrained demand, +$37 at unconstrained demand. One utility, and only the generation and transmission part of the bill. The same report found that datacenters "are currently paying full cost of service, but growing energy demand is likely to increase costs for other customers".

bill-va-2040-year
the Virginia projection, as a yearly amount
$168 to $444 a year
… to 444
cost derivedThis site, 2026. Bottom-up model, derived on the sources page
verified 2026-10-01
$14 × 12 to $37 × 12inputs: bill-va-2040

About 46 cents to $1.22 a day by 2040. Against the $90 a month these charges were in 2023, a rise of 16% to 41%.

res-price-2020
US average residential electricity price, 2020
13.15 cents/kWhcost governmentUS EIA, 2026. Electric Power Monthly, table 5.3, average price of electricity to ultimate customers
verified 2026-10-01
res-price-2025
US average residential electricity price, 2025
17.30 cents/kWhcost governmentUS EIA, 2026. Electric Power Monthly, table 5.3, average price of electricity to ultimate customers
verified 2026-10-01
res-price-rise
rise in the US average residential electricity price, 2020 to 2025
32%cost governmentUS EIA, 2025. Today in Energy, May 2025, on rising retail electricity prices
verified 2026-10-01
17.30 ÷ 13.15 − 1 = 31.6%inputs: res-price-2025, res-price-2020

Not adjusted for inflation. EIA does not attribute a share of the rise to datacenters; its May 2025 analysis points to capital spending on aging generation and delivery infrastructure.

va-scc-2026
rise in the typical Dominion residential bill for 2026 approved by Virginia's regulator
$11.24 a monthcost governmentVirginia State Corporation Commission, 2025. Final Order in the Dominion biennial review, PUR-2025-00058, 25 November 2025
verified 2026-10-01

From the biennial review order, with a further $2.36 a month in 2027. The commission's release does not attribute the increase to datacenters. The same order created the separate rate class for very large customers.

pjm-dc-share
share of capacity charges across the last four PJM auctions tied to datacenter demand, existing and forecast
46.2%cost independent-estimateMonitoring Analytics (PJM Independent Market Monitor), 2026. Market Monitor Report to the PJM Members Committee, 27 July 2026
verified 2026-10-01

A counterfactual simulation by the market monitor that includes forecast load not yet built. Wholesale dollars, which reach household bills to different degrees by state and utility. PJM is the grid operator for 13 mid-Atlantic and midwestern states.

pjm-dc-dollars
capacity charges across the last four PJM auctions tied to datacenter demand
$29.4 billioncost independent-estimateMonitoring Analytics (PJM Independent Market Monitor), 2026. Market Monitor Report to the PJM Members Committee, 27 July 2026
verified 2026-10-01

Same basis and caveats as the 46.2% share.

lbnl-load-price
fall in average retail price associated with a 10% rise in a state's electricity use, 2019 to 2024
0.6 cents/kWhcost governmentLawrence Berkeley National Laboratory and Brattle, 2025. Factors Influencing Recent Trends in Retail Electricity Prices in the United States, October 2025
verified 2026-10-01

Load growth "has tended to depress retail electricity prices in recent years, by spreading fixed costs over greater load". Residential customers benefited to a lesser extent, and the authors warn the relationship "need not always exist". The April 2026 update found it held through 2025.

This site is independent. No organization named on it has reviewed or endorsed it. Company and product names are used only to identify the source of a published figure. All marks belong to their owners.

This page's own footprint

Measuring.

With scripting off this page cannot measure itself. Its transfer is a few hundred kilobytes; at 0.06 kWh/GB that is well under 2.42 Wh, and a few minutes on a ≈3 W phone adds about the same again.

Device assumption

Method: bytes transferred from the browser's own resource timing, times network intensity; plus time this page has been open, times the device draw implied by the digital-day rows. Server and CDN energy are not measured. If this figure ever exceeds a day of AI use, the build has failed its own budget and something must come out.